Canada › General Construction › Spinkler Head Replacement - Matsqui Complex

Spinkler Head Replacement - Matsqui Complex

Cancelled

Correctional Service of Canada (CSC) sought bids for this general construction requirement in British Columbia. Traditional competitive process with a formal solicitation. The lowest compliant price wins. Bidders had 15 days between publication and closing.

BuyerCorrectional Service of Canada (CSC)
Delivery regionCanada, British Columbia, Abbotsford
Closing date2026-01-27 17:00
Published2026-01-12
TradeGeneral Construction
Solicitation no.21807-25-0078A

Key dates

  • Published January 12, 2026 304 days ago
  • Bids close January 27, 2026 289 days ago
  • Contract starts February 2, 2026 283 days ago
  • Contract ends March 31, 2026 226 days ago

Work is expected to start about 6 days after bids close. Planned duration: about 57 days.

What the buyer is asking for

Sprinkler Head Replacement – Matsqui Complex

This requirement is for: The Correctional Service of Canada.

Trade agreement: Canadian Free Trade Agreement (CFTA)

Policy on Reciprocal Procurement: This solicitation is open only to Canadian suppliers.

Competitive Procurement Strategy: Lowest priced compliant bid.

Set-aside under the Procurement Strategy for Indigenous Business: This procurement is not subject to any set-asides for Indigenous Suppliers.

Comprehensive Land Claim Agreement: This procurement is not subject to a Comprehensive Land Claims Agreement.

Security Requirements: This contract does not include security requirements.

Nature of Requirements:

The following is a summary of the statement of work for this requirement.

The Correctional Service of Canada has a requirement to replace sprinkler heads that have expired due to age and require lifecycle replacement for buildings in the Matsqui Complex. That complex includes the following institutions: Pacific, Matsqui and Fraser Valley. The work will involve the following:

Show the full description

1.1 Background:

The Correctional Service of Canada’s recent annual fire inspection Contractor has provided Matsqui Complex with reports indicating the sprinkler heads are due for replacement in multiple buildings.

1.2 Objectives:

To replace the existing deficient sprinkler heads with the same or equivalent make and model to ensure fire suppression continuity in accordance with the building’s original fire suppression design specifications and NFPA 13 standards.

1.3 Tasks Matsqui Institution:

1.3.1 The Contractor must isolate and drain the sprinkler systems in building M3, Living Unit 1, Living Unit 2 and Living Unit 3 and remove and replace deficient sprinkler heads of the following make and model, in the following quantities: Living Unit 1: V2707 = 90 heads K5.6 155°F V2709 = 108 heads K5.6 155°F

Living Unit 2: V2707 = 90 heads K5.6 155°F V2709 = 108 heads K5.6 155°F

Living Unit 3: V2707 = 90 heads K5.6 155°F V2709 = 108 heads K5.6 155°F

1.4 Tasks Fraser Valley Institution:

1.4.1 The Contractor must isolate and drain the sprinkler systems in building A, B, D, F and G and remove and replace deficient sprinkler heads of the following make and model, in the following quantities:

Building A: TY3231 = 97 heads K80.6 68°C TY3131 = 14 heads K80.6 93°C TY3131 = 6 heads K80.6 68°C TY3335 = 3 heads K80.6 68°C

Building B: TY3231 = 42 heads K80.6 68°C TY3131 = 25 heads K80.6 93°C TY3131 = 44 heads K80.6 68°C TY3331 = 1 head K80.6 68°C

Building D: VK-302 = 40 heads K 5.6 200°F VK-410 = 22 heads K 5.6 165°F VK-442 = 4 heads K 5.6 200°F VK-300 = 3 heads K 5.6 200°F

Building F: V2708 = 71 heads K80.75 68°C V2726 = 26 heads K80.75 79°C V2710 = 6 heads K 5.6 68°C V2710 = 2 heads K80.75 79°C V2716 = 11 heads K80.75 93°C C3201 = 55 heads K 5.6 155°F C3101 = 8 heads K 5.6 200°F BB-117 = 27 heads K112.4 100°C SD1 = 10 heads K80.75 100°C

Building G: C2296 = 12 heads K 4.3 155°F C2296 = 1 head K 4.3 200°F

1.5 Tasks Pacific Institution:

1.5.1 The Contractor must isolate and drain the sprinkler systems in Building A and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.2 The Contractor must isolate and drain the sprinkler systems in Building B and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.3 The Contractor must isolate and drain the sprinkler systems in Building C and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.4 The Contractor must isolate and drain the sprinkler systems in Building D and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.5 The Contractor must isolate and drain the sprinkler systems in Building F and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.6 The Contractor must isolate and drain the sprinkler systems in Building F8 and remove and replace deficient sprinkler heads of the following make, model and quantities:

TY3231 = 19 heads K5.6 68°C TY3131 = 5 heads K5.6 68°C V3301 = 6 heads K5.6 68°C 1.5.7 The Contractor must isolate and drain the sprinkler systems in Building G and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.8 The Contractor must isolate and drain the sprinkler systems in Building H and remove and replace deficient sprinkler heads of the following make, model and quantities:

1.5.9 The Contractor must isolate and drain the sprinkler systems in Building J and remove and replace deficient sprinkler heads of the following make, model and quantities:

GL4231 = 13 heads K4.2 68°C GL4110 = 10 heads K4.1 68°C

1.5.10 The Contractor must isolate and drain the sprinkler systems in Building N and remove and replace deficient sprinkler heads of the following make, model and quantities:

V3201 = 22 heads K5.6 68°C VK3101 = 9 heads K5.6 121°C TY3131 = 3 heads K5.6 93°C

1.5.11 The Contractor must isolate and drain the sprinkler systems in Building P and remove and replace deficient sprinkler heads of the following make, model and quantities:

TY3131 = 30 heads K5.6 68°C VK3101 = 8 heads K5.6 121°C V3301 = 9 heads K5.6 68°C

1.5.12 The Contractor must isolate and drain the sprinkler systems in Building Q remove and replace deficient sprinkler heads of the following make, model and quantities:

TY3231 = 66 heads K5.6 68°C

1.5.13 The Contractor must isolate and drain the sprinkler systems in Building S and remove and replace deficient sprinkler heads of the following make, model and quantities:

Requirements mentioned in the notice

  • Set-aside / eligibility “Set-aside under the Procurement Strategy for Indigenous Business: This procurement is not subject to any set-asides for Indigenous Suppliers.”

Extracted from the notice text. Always read the full solicitation documents for the exact requirements.

Who can bid and how it is decided

  • Process Competitive - Traditional Traditional competitive process with a formal solicitation.
  • How the winner is chosen Lowest Price The lowest compliant price wins.
  • Trade agreements See notice
  • Goods & services category Fire protection, Fire prevention, Fire sprinkler systems, Fire sprinkler heads

Documents attached to the notice

View the official CanadaBuys notice → (reference cb-872-39032453)

This tender is cancelled. See open general construction tenders.

Voir en français

More general construction tenders in British Columbia

Correctional Service of Canada (CSC) has 43 tenders in our database, typically open for about 22 days. See the buyer profile →

Other tenders from Correctional Service of Canada (CSC)